Tel:0512-57503576
Aston group

68.png

H13 and h14 high efficiency filter with diaphragm

  Performance description

  External process: galvanized steel plate or aluminum profile, surface oxidation.

  Filter material separation: aluminum foil corrugated plate.

  Filter material: water resistant glass fiber filter paper.

  Sealant: polyurethane. Gasket: EVA.

  Main uses: for cleaning room, commercial and industrial ventilation and air conditioning system

  The main overspeed governor is equipped with ventilation and air conditioning system with tight space.

  Over concentration efficiency:

  H13(EN 1822)≥99.95atMPPS; H14 (EN 1822) ≥ 99.995atmpps: the efficiency can be tested one by one before leaving the factory, which meets the current national specifications; MPPs = most easily penetrated particle size; Continuous operation temperature ≤ 80 ℃; Moisture resistance ≤ 100% RH; The maximum final resistance is recommended to be ≤ 450pa.